Derating curve for the 1771-oq output module – Rockwell Automation 1771-OQ/B Isolated 24V dc Output Module Installation Instructions User Manual

Page 10

Advertising
background image

Publication 1771-IN081B-EN-P - June 2004

10 Isolated 24V dc Output Module

Derating Curve for the 1771-OQ Output Module

Emmisions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open-style)

Fuse

2.5A, 250V normal blow fuse, Cooper Bussman AGC 2.5 or Littelfuse
31202.5

Field Wiring Arm

Cat. No. 1771-WF

Wiring Arm Screw Torque

7 pound-inches (0.8Nm)

Conductors

Wire Size

Category


14AWG (2.5mm

2

) stranded copper rated at 60°C or greater

3/64 inch (1.2mm) insulation (maximum)

2

1

Certification (when product is
marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CE

2

European Union 89/336/EEC EMC Directive, compliant with:

EN 50082-2, Industrial Immunity

EN 61326, Meas./Control/Lab., Industrial Requirements

EN 61000-6-2, Industrial Immunity

EN 61000-6-4, Industrial Emissions

C-Tick

2

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11, Industrial Emissions

1 You use this conductor category information for planning routing as described in publication 1770-4.1, Industrial Automation

Wiring and Grounding Guidelines.

2 See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details.

Specifications

0

0.25

0.5

0.75

1.0

1.25

1.50

1.75

2.0

2.25

0

1 0

20

30

40

50

60

T emperature (˚C)

Module Output

C

urrent - A

2.50

Advertising