Specifications – Rockwell Automation 1771-OQ/B Isolated 24V dc Output Module Installation Instructions User Manual

Page 9

Advertising
background image

Publication 1771-IN081B-EN-P - June 2004

Isolated 24V dc Output Module 9

Specifications

Specifications

Outputs per Module

8 (4 groups of 2, each group sharing a common dc supply)

Module Location

1771-A1B, thru -A4B or later I/O chassis

Output Voltage Range

24V dc, 2.25A, 4A inrush derated linearly from 37°C to 1.25A, 24V dc
@ 60°C

2.25A per group derated linearly from 37°C to 1.25A

Maximum Output Current

2.25A per output

2.25A per group

9.0A per module

Maximum Surge Current

4.0A for 10ms per output

Maximum On-state Voltage
Drop

2V dc @ 2.25A

Maximum Off-stage Leakage
Current

1.0mA per output @ 34V dc, 25°C

Maximum Power Rating

4.5W per output

Output Signal Delay

10ms on or off

Power Dissipation

19.1W (max.), 1.1W (min.)

Thermal Dissipation

65.1 BTU/hr (max.), 3.75 BTU/hr (min.)

Backplane Current

225mA @ 5V

Isolation Voltage

50V continuous, tested to withstand 500V for 60s

Envitonmental Conditions

Operating Temperative

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):

5 to 95% noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2g @ 10-500Hz

Radiated RF Immunity

IEC 61000-4.3

10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4.4

±1kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4.5

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4.6

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz

Advertising