10 Remote I/O Scanner

Publication 1747-IN060D-EN-P - November 2002

RIO Link Wiring

The scanner is connected to other devices on the RIO link in a daisy-chain (serial)
configuration. There are no restrictions governing the space between each device,
provided the maximum cable distance (Belden 9463) is not exceeded. A 1/2 watt
terminating resistor (included with the module) must be attached across line 1 and
line 2 of the connectors at each end (scanner and last physical device) of the RIO
link. The size of the resistor depends on the baud rate and extended node

capability, as shown in the table below.

Note: To use extended node, all devices on the RIO link must support it. Refer to

each device’s user manual.

Baud Rate

Max. Cable Distance
(Belden 9463)

Resistor Size

Using Extended
Node Capability

57.6K baud

3048 m (10,000 ft.)

82

1/2 Watt Gray-Red-Black-Gold

115.2K baud

1524 m (5,000 ft.)

230.4K baud

762 m (2,500 ft.)

Not Using
Extended Node
Capability

57.6K baud

3048 m (10,000 ft.)

150

1/2 Watt Brown-Green-Brown-Gold

115.2K baud

1524 m (5,000 ft.)

230.4K baud

762 m (2,500 ft.)

82

1/2 Watt Gray-Red-Black-Gold

RIO Scanner

RIO Link

Connector

Terminating Resistor Last

Physical Device End

Terminating Resistor

Scanner End

Shield Drain Wire

(For Series A Retrofits)

Shield Drain Wire

(For New Series B Installations)

Ring Lug

Chassis Mounting

Bracket

RIO Link

Connector

Line 1 – Blue

Shield – Shield

Line 2 – Clear