Required Tools and Equipment

Have the following tools and equipment ready:

medium blade screwdriver

termination kit (the package, containing resistors and a ring lug, which was
included with the scanner)

approximately 38 cm (15 inches) of #20 AWG wire for grounding the drain
shield to the SLC chassis (for Series A retrofits)

adequate length of RIO communication cable (Belden™ 9463) for your
specific application

Installation

Make sure you have set the DIP switch properly before installing the scanner.

Insertion

IMPORTANT

Before installation, make sure that your modular SLC power
supply has adequate reserve current capacity. The scanner
requires 600 mA at 5V dc.