Programming and operation chapter 3 – Rockwell Automation 1771-IS 5V DC INPUT MOD User Manual

Page 42

Advertising
background image

Programming and Operation

Chapter 3

3-23

NOTES:

B001:0010

15

U

B002:0000

00

T0001

15

L

B002:0000

00

EN

DN

CNTL

12

CNTL

15

B002:0000

ER

CNTL

13

00

BLOCK XFER DONE

T0001

/

TE

T0001

17

TD

T0001

15

PLC–3 Block Transfer

b) Timer allows at least 20ms between block transfers.

a) Module located in rack 1, module group 2, slot 1.

TIMER DONE

BTR
BLOCK XFER READ
RACK :
GROUP :
MODULE:
DATA:

001

2

1 = HIGH

FD002:0012

LENGTH:
CNTL:

3

FB001:0010

TON

TIMER ON T0001
0.01 SECOND
TP = 2
TA = 0

Diagnostics

Bit 12 of the block transfer diagnostic word is the communication fault
bit. A communication fault can be caused either by cycling power to the
processor, by a break in I/O communications or by excessive electrical
noise radiating into the I/O communication cable. This bit will go ON if
the transfer is aborted. The I/O communication cable and system
grounding should be checked thoroughly in accordance with grounding
and shielding recommendations presented in the processor Assembly and
Installation Manual. This bit can be reset only by cycling power to the
module.

Data Buffering

Data that is block transferred to the data table should be buffered before it
is used to guard against the manipulation of invalid data by subsequent
user program instructions.