Rockwell Automation 1771-IS 5V DC INPUT MOD User Manual

Page 9

Advertising
background image

Module Preparation, Wiring, and
Installation

Chapter 2

2-2

Figure 2.1
Mode Selection Dip Switch

1

ON

Always OFF

2

ON

16–Bit Data

3

ON

Fast

4

ON

Momentary (Latched) Contact Mode

5

ON

Always OFF

6

ON

Always OFF

7

ON

Program Initiated Reset

ON

OFF

ON

OFF

ON

OFF

O

O

1

2

3

4

5

6

7

10362

OFF

OFF

OFF

OFF

OFF

OFF

OFF

12–Bit Data

Normal

Maintained Contact Mode

Automatic Reset

N

F
F

Switch #1 - Always OFF.

Switch #2 - 16 Bit Storage/12 Bit Storage, Select 12-bit storage when
using 3-digit BCD thumbwheel switches. Select 16-bit storage when
using 4-digit BCD thumbwheel switches, discrete momentary contact
switches, or discrete maintained contact switches. (ON for 16-bit storage,
OFF for 12-bit storage.)

Switch #3 - Normal Scan/Fast Scan. The module scan is independent of
the processor scan and is generally set at the normal (15.3 msec) position.
The fast scan (5.1 msec) can be used when operating in either the

Advertising