46 1734/1738 I/O Module Assembly Information

Very High Speed Counter Modules

Use the tables shown below for the following modules:

• 1734-VHSC5
• 1734-VHSC25 or 1738-VHSC24M23

The modules support 3 different consumed output data assemblies. The
Active Output Assembly field of the Configuration assembly selects which
output assembly will be used. Assembly 105 is the default. Other produced
assemblies are possible but require separate configuration of the module. For
more information regarding the specific fields of these assemblies, consult the
product's user manual.

Consumed Output Data Assembly 34

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Ch 7

Ch 6

Ch 5

Ch 4

Ch 3

Ch 2

Ch 1

Ch 0

Produced Input Data Assembly 102

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Stored Channel Data [Low Byte]

1

Stored Channel Data [1]

2

Stored Channel Data [2]

3

Stored Channel Data [High Byte]

4

Status (Low Byte)

5

Status (High Byte)

Consumed Output Data Assembly 105

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Counter Control

1

Output Control

Consumed Output Data Assembly 106

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

PWM Value (Low Byte)

1

PWM Value (High Byte)