Rockwell Automation 1791-32AO SERIES B 32 Input AC Block I/O Module User Manual

32 input ac block i/o module, Installation

Advertising
background image

1

32 Input AC Block I/O Module

Cat. No. 1791-32A0 Series B

Installation

Mount the block I/O module in a vertical (recommended) or horizontal position.
Allow sufficient room around the block for cooling air to flow through the block
module. Refer to Figure 1.

Figure 1
Mounting Dimensions for the Block I/O Module
Cat. No. 1791–32A0 (PLC version shown)

2 mounting holes
for #8 screws

1

30

4.35

(110.5)

3.35

(85.1)

6.95

(176.5)

6.60

(167.6)

0.5

(12.7)

6.95H x 4.35W x 3.85D
(176.5H x 110.5W x 98D)

Inches

(Millimeters)

Equipment

Grounding Stud

CAUTION: When tightening grounding
stud nut, do not exceed 15 in-lbs.

Block

Operating temperature
in air gap below module
must not exceed 60

o

C

(140

o

F).

2.0 (50.8) air gap

on all 4 sides.

30

1

1791-32A0

120V ac INPUT

IN

IN

00
01
02
03
04
05
06
07

10
11
12
13
14
15
16
17

00
01
02
03
04
05
06
07

10
11
12
13
14
15
16
17

G

G+1

00
01
02
03
04
05
06
07

10
11
12
13
14
15
16
17

G

(G+1)

00
01
02
03
04
05
06
07

10
11
12
13
14
15
16
17

COMM

STATUS

RACK #

ALLENĆBRADLEY

Dimensions