Block I/O
Cat. No. 1791-32A0 Series B

9

The SLC 500 controllers communicate with the block I/O using an I/O Scanner
module (cat. no. 1747-SN series A). Refer to the user manual for the 1747-SN/A
Scanner module for more information.

Important: This block I/O module is not compatible with the 1747-DSN
Distributed I/O Scanner module.

Termination Resistor

A termination resistor must be installed on the last block in a series. Connect the
resistor as shown in Figure 7.

Figure 7
Installing the Termination Resistor

Termination

Resistor

Connect termination resistor across
terminals 6 (BLU) and 8 (CLR).

10835–I

BLU

SHD

CLR

150 ohm – 57.6K and 115.2K baud
82 ohm – 230.4K baud

ATTENTION:

Devices that are operating at 230.4K baud must have

82 ohm terminators in place for proper operation.