12 Allen-Bradley Power Supply Modules

Specifications

1771-P4S

1771-P6S

1771-P4S1

1771-P6S1

Input Voltage

120V ac, 0.9A

220V ac, 0.5A

100V ac, 1.06A

200V ac, 0.53A

Input Range

97-132V ac rms

194-264V ac rms

85-120V ac rms

170-240V ac rms

Frequency

47-63Hz

47-63Hz

47-63Hz

47-63Hz

Fuse

250V, 1.5A, Bussman MDL 1.5, Littelfuse 31301.5, IEC 127 Type T (Blue)

Output Voltage (backplane)

5V dc

Output Current (maximum)

8A (see derating curve below)

Power Dissipation

16W

Thermal Dissipation

47.8 BTU/hr

Adjacent Slot Power Dissipation

10W maximum

Branch Circuit Protection

1

15A maximum (user supplied)

Environmental Conditions

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-25 to 80°C (-13 to 176°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating
Damp Heat):
5 to 95% noncondensing

Shock

Operating

Non-operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30g peak acceleration
50g peak acceleration

Vibration

IEC 60068-2-6, (Test Fc, Operating)
Tested 2g @ 10-500Hz

Isolation Voltage

Tested to withstand 1000V ac for 60s

Enclosure Type Rating

None (open style)

Conductors

Wire Size

Category

14AWG (2.4mm

2

) maximum, solid or stranded copper wire rated at 60°C or greater

3/64 inch (1.2mm) insulation maximum
1

2

5 Position Terminal Block

A-B PN 941274-55, Wago

3

PN 231-002/027-000 (1 included with each power supply)

Certifications (when product is marked)

UL

UL Listed Industrial Control Equipment, certified for US and Canada

C-UL UL Listed for Class I, Division 2, Groups A, B, C and D Hazardous locations,

certified for Canada

CE

4

European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN61326; Meas./Control/Lab Industrial Requirements

EN 61000-2; Industrial Emissions
European Union 73/23/EEC LVD Directive, compliant with:
EN 61131-2, Programmable Controllers

C-TicK

4

Australian Radiocommunications Act compliant with:

AS/NZS 2064, Industrial Emissions

1

Provided in all ungrounded mains connections.

2

.Use this conductor category information for planning conductor routing as described in publication 1770-4.1, “Industrial Automation Wiring and Grounding Guidelines

3

Wago Corporation, 9085 N. Deerbrook Trail, Brown Deer WI 53223

4

See the Product Certification link at

www.ab.com for Declaration of Conformity, Certificates, and other certification details