6 SLC 500™ 32-Channel Digital I/O Modules
Publication 1746-IN028A-EN-P - October 2003
Specifications
Input Module Specifications
Description:
Specification: 1746-
(1)
(1)
Series A, B and C 32-point input modules are fused to protect external wiring, one fuse per common. The fuses are
non-replaceable and are rated at 2.5A. Series D 32-point input modules are not fused.
IB32
IV32
Voltage Category
24
Number of Inputs
32
Points per Common
8
Operating Voltage
15 to 30V dc at 50
°
C
15 to 26.4V dc at 60
°
C
Sink
15 to 30V dc at 50
°
C
15 to 26.4V dc at 60
°
C
Source
Backplane Current Consumption
5V
0.050A
24V
0A
Isolation from Backplane
1500V ac for 1 min.
Signal Delay (max.)
on = 3 ms
off = 3 ms
On State Voltage (min.)
15.0V dc
Off State Voltage (max.)
5.0V dc
Off State Current (max.)
1.5 mA
Nominal Input Current at 24V dc
5.1 mA at 24V dc
Heat Dissipation Watts per point
0.20
Heat Dissipation Watts (min.)
0.25
Heat Dissipation Total Watts
6.65