Distributed complete mode – Rockwell Automation 1772-LP3 PLC - 2/30 Programmable Controller Programming and Operations Manual User Manual
Page 222

Data Transfer File Instructions
Chapter 12
12Ć7
Figure 12.6
Status Bits for Complete Mode
Rung Condition
Enable Bit (17)
Done Bit (15)
Instruction Operation
1
Scan
A = Status bits are reset to zero and
counter is reset to word 1.
Distributed Complete Mode
In cases where is is not necessary that the file operation be completed in
one program scan, it may be advantageous to distribute the file operation
over several program scans. This is to avoid overextending the scan time of
any one program scan. This scan can be done by selecting the distributed
complete mode. Any rate per scan, R, can be chosen where 0<R<4 file
length.
When the rung containing the file instruction goes true, the number of
words equal to the rate per scan is operated upon during one scan. This
process is repeated over a number of scans, until the entire file has been
operated upon. Figure 12.7 shows the operation of the file instruction in
the distributed complete mode.