Wire connections for the 1794-tb3gt – Rockwell Automation 1794-TB3GT Flex I/O Terminal Base Units Installation Instructions User Manual

Page 3

Advertising
background image

FLEX I/O Grounded Cage Clamp Temperature Terminal Base Unit 3

Publication 1794-IN133A-EN-P - May 2012

5. Rotate the terminal base onto the DIN rail with the top of the rail

hooked under the lip on the rear of the terminal base. Use caution to
make sure that the female FlexBus connector does not strike any
of the pins in the mating connector.

6. Refer to the installation instructions for specific wiring information

for the module you are installing in this terminal base.

7. Repeat the above steps to install the next terminal base.

Wire Connections for the 1794-TB3GT

ATTENTION

When using FLEX I/O modules in a high-vibration installation,
especially when mounting the DIN rail vertically, use DIN-rail locks
(A-B part number 1492-EA35) to prevent accidental separation of the
terminal block units.

C

Make sure the hook (C) on the terminal base slides under the
edge of the adapter and the FlexBus connector is fully retracted.
Slide the terminal base over, tight against the adapter.

Press down on the terminal base to lock it on the DIN rail. If the
terminal base does not lock into place, use a screwdriver or
similar device to open the locking tab, press down on the base,
and release the locking lever to lock the base in place.

Gently push the FlexBus connector into the side of the side
of the adapter to complete the backplane connection.

IMPORTANT

The 1794-TB3GT terminal base is for use with 1794-IRT8 and
1794-IRT8XT, Series B modules only.

ATTENTION

Do not wire more than 2 conductors on any single terminal.

ATTENTION

The wiring on this base unit is different from other terminal base
units in FLEX I/O. Make certain that connections are correct before
applying power.

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

34

Ch0

Ch4

24V DC

Supply

In

d

n

G

d

n

G

24V DC

Supply

Out

+V

C

V

+

M

O

COM

6 Chassis

Ground

for Shields

Chassis Ground

Chassis Ground

+

H

+

H

+

H

+

H

+

H

+

H

+

H

+

H

L

-

L

-

L

-

L

-

L

-

L

-

L

-

-

L

Ch1

Ch5

Ch2

Ch6

Ch3

Ch7

CJC1

CJC2

+24V DC = Terminals C-34, C-50
COM = C-35, C-51
Chassis Ground = Terminals B-16, B-33, C-38, C-40…45, C-47

Ch0 = A-0…A-1, B-17…B-18

Channel grouping:

Ch1 = A-4…A-5, B-21…B-22

Ch2 = A-8…A-9, B-25…B-26

Ch4 = A-2…A-3, B-19…B-20

Ch5 = A-6…A-7, B-23…B-24

Ch3 = A-12…A-13, B-29…B-30

Ch7 = A-14…A-15, B-31…B-32

Ch6 = A-10…A-11, B-27…B-28

For daisy-chaining: Supply in - C-34 (+), C-35 (-)

Supply out - C-50 (+), C-51 (-)

CJC1 tail = A1
CJC2 tail = A14