4 FLEX I/O Grounded Cage Clamp Temperature Terminal Base Unit

Publication 1794-IN133A-EN-P - May 2012

Typical Wiring Guidelines

Specifications

ATTENTION

Total current draw through the terminal base unit is limited to 10 A.
Separate power connections may be necessary.

Wiring when total current draw is less than 10 A

Wiring when total current draw is greater than 10 A

Daisy-chaining

Individual

Combination

24V DC

24V DC

24V DC

24V DC

24V DC

24V DC

Note: Use this configuration if using any
“noisy” DC digital I/O modules in your system.

Thermocouple Module wiring separate from discrete wiring.

Note: All modules powered by the same power supply
must be analog modules for this configuration.

Note: All modules must be analog modules for this configuration.

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

Thermocouple

or Analog Module

General

Attribute

Value

Terminal screw
torque

0.79...1.02 Nm (7…9 lb-in.)

Current capacity,
max

V/COM terminals: 10 A
I/O terminals: 2 A

FlexBus current

5V DC, 640 mA

Voltage rating,
max

V/COM terminals: 31.2V DC/AC, 50/60 Hz

Isolation voltage

50V (continuous), Basic Insulation Type
Tested at 500V for 60 s, Field to FlexBus, or installed module.

Enclosure type
rating

None (open-style)

Wire size

0.21... 1.3 mm

2

(24…16 AWG) stranded copper wire rated at

75 °C (167 °F ) or greater, 1.2 mm (3/64 in.) insulation max

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1.

Established by installed module

North American
temp code

T4A

IEC temp code

T4

Dimensions,
approx.
(HxWxD)

94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)
(with module installed in terminal base)