16 Compact™ 16-Point AC/DC Relay Output Module

Publication 1769-IN062A-EN-P - December 2001

Relay Contact Ratings

Volts (max.)

Continuous Amps
per Point (max.)

(1)

(1)

The continuous current per module must be limited so the module power does not exceed 1440 VA.

Amperes

(2)

(2)

Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
1770-4.1.

Voltamperes

NEMA
ICS 2-125

Make

Break

Make

Break

240V ac

2.5A

7.5A

0.75A

1800 VA

180 VA

C300

120V ac

15A

1.5A

125V dc

1.0A

0.22A

(3)

(3)

For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 48V, the make/break ratings for
relay contacts cannot exceed 2A.

28 VA

R150

24V dc

2.0A

1.2A

(3)