Rockwell Automation 1771-OD AC (120V) Isolated Output Module Installation Instructions User Manual
Page 12
AC (120V) Isolated Output Module
12
Publication 1771-IN078A-EN-P - October 2002
Fuses
5A, 250V Bussman MTH5, IEC 127 Type F
Field Wiring Arm
Cat. No. 1771-WD
Field Wiring Arm Screw Torque
7-9 pound-inches (0.8-1.0Nm)
Conductors
Wire Size
Category
14-22AWG (2.5-0.25mm
2
) stranded copper wire rated at 75
o
C or
greater
1
3/64inch (1.2mm) insulation (max)
1
2
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
1 One or two 14-22 AWG solid or stranded copper wires per terminal. Must be same size. Do not intermix solid and stranded wires.
Use copper wire only.
2 Use this conductor category information for planning conductor routing . Refer to publication 1770Ć4.1, Industrial Automation Wiring and
Grounding Guidelines."
Publication 1771-IN078A-EN-P - October 2002
Supersedes Publication 1771Ć2.12 - April 1990
PN957689-80
Copyright 2002 Rockwell International, Inc. Printed in USA