AC (120V) Isolated Output Module

9

Publication 1771-IN078A-EN-P - October 2002

You can use an output of the 1771–OD module to drive an input of a
120V AC input module (1771–IA, –IA2, –ID and –IAD) to indicate
status, such as the turning on of a motor starter (Figure 2). Both
modules must be powered by the same ac source. In addition, you
must add an external resistor (or an electronic snubber, pt. no.
RG–1676–1) between the output terminal and the common (L2)
(Figure 2). Typically, this is a 2.5K ohm, 10W resistor.

ATTENTION

!

Do not connect the 1771-OD output channels in
series. Doing so can result in distortion of the output
waveform causing the output devices to chatter.

Figure 2

Using an Output Module to drive an Input Module

L1

2.5K ohm

10 Watt