Mount the Adapter and I/O Base
To mount the ArmorPOINT I/O adapter on a wall or panel, use the screw holes provided 
in the adapter. A mounting illustration for the ArmorPOINT adapter with several 
attached I/O bases is shown below. 
Mounting illustration for ArmorPOINT I/O adapter with I/O Mounting bases
Install the adapter and its I/O Mounting base as follows:
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for M4 (#8) machine or self-tapping screws.
3. Mount the adapter using M4 (#8) screws.
ATTENTION: This product is intended to be mounted to a well-grounded 
mounting surface such as a metal panel. Additional grounding connections 
from the power supply's mounting tabs or DIN rail (if used) are not required 
unless the mounting surface cannot be grounded. Refer to Industrial 
Automation Wiring and Grounding Guidelines, Rockwell Automation 
publication 
, for additional information.
ATTENTION: To comply with the CE Low Voltage Directive (LVD), this 
equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Adapter
46.2 mm
(1.82 in)
52.0 mm
(2.05 in)
20.0 mm
(0.79 in)
20.0 mm
(0.79 in)
52.0 mm
(2.05 in)
52.0 mm
(2.05 in)
44834
102 mm
(4.02 in)
56 mm
(2.20 in)