Install the adapter – Rockwell Automation 1734-AENTR, Series B 1734 POINT I/O Dual Port EtherNet/IP Adapter Installation Instructions User Manual
Page 9

1734 POINT I/O Dual Port EtherNet/IP Adapter 9
Publication 1734-IN041B-EN-P - October 2013
Install the Adapter
Follow this procedure to install the adapter on the DIN rail.
Mount the POINT I/O Dual Port EtherNet/IP Adapter on a DIN Rail
Position the I/O adapter vertically above the DIN rail. Make sure that the DIN rail lock is
in horizontal position.
1. Position the adapter module on an IEC standard (35 x 7.5 x 1 mm) top-hat DIN
rail at a slight angle (DIN rail: Allen-Bradley part number
199-DR1; 46277-3;
EN50022).
ATTENTION: You must only use Series C POINT I/O modules with
1734-AENTR EtherNet/IP Adapters. Series A or Series B POINT I/O modules
will not work with 1734-AENTR EtherNet/IP Adapters (does not apply to
POINTGuard modules).
1734-AENTR Series B
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I O
75.30
(2.96)
74.00
(2.91)
132.72
(5.23)
52.23
(2.06)
35.55
(1.40)
A
B
45174
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)