8 GuardPLC Digital Input Module

Rockwell Automation Publication 1753-IN004C-EN-P - June 2010

Digital Input Terminals

Terminals accommodate wires up to 1.5 mm

2

(16 AWG). See the terminal torque specifications

on page

12

. Digital inputs (DI) are connected to the following terminals.

LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only its four related
inputs.

Terminal Number

Designation

Function

1

LS+

Sensor supply for inputs 1…4

2

1

Digital input 1

3

2

Digital input 2

4

3

Digital input 3

5

4

Digital input 4

6

L-

Reference pole

7

LS+

Sensor supply for inputs 5…8

8

5

Digital input 5

9

6

Digital input 6

10

7

Digital input 7

11

8

Digital input 8

12

L-

Reference pole

13

LS+

Sensor supply for inputs 9…12

14

9

Digital input 9

15

10

Digital input 10

16

11

Digital input 11

17

12

Digital input 12

18

L-

Reference pole

19

LS+

Sensor supply for inputs 13…16

20

13

Digital input13

21

14

Digital input 14

22

15

Digital input 15

23

16

Digital input 16

24

L-

Reference pole

1

LS+-

LS+

LS+

LS+

L-

DI

2 3 4

1 2 3 4 5 6

5

L-

DI

6 7 8

7 8 9 10 11 12

9

L-

DI

10 11 12

13 14 15 16 17 18

13

L-

DI

14 15 16

19 20 21 22 23 24

1 2 3 4 5 6

7 8 9 10 11 12

13 14 15 16 17 18

19 20 21 22 23 24

Advertising