background image

Isolated Analog Input Module

4

Publication 1771Ć5.62 - November 1998

The module has configuration jumpers for determining the input type
(voltage or current) for each input. The module is shipped with the
configuration jumpers positioned for voltage mode.
You can
select either voltage or current for each input.

Key the Backplane

Connector

Place your module in any slot in the chassis
except the leftmost slot which is reserved for
processors or adapters.

ATTENTION: Observe the
following precautions when
inserting or removing keys:

insert or remove keys with
your fingers

make sure that key placement
is correct

Incorrect keying or the use of a
tool can result in damage to the
backplane connector and possible
system faults.

!

Position thekeying bands in thebackplaneconnectors to correspond to

thekey slots on themodule.

Placethekeying bands:

between 10 and 12

between 32 and 34

You can changetheposition of thesebands if

subsequent system design and rewiring makes

insertion of a different type of module necessary.

Upper

Connector

11022ĆI

I/O chassis

Setting the Configuration

Jumpers

Remove the four screws securing the side cover to

themoduleand removethecovers.

19805

1

Reposition the configuration jumpers associated with each input

channel according to your requirements.

2

The module is shipped with each channel set for voltage mode. If

current mode is desired, you must set a jumper for each channel on

themodulecircuit board. You can mix voltagemodeand current

modesettings.

= Configuration Jumper

Voltage

Mode

Current

Mode

Enlarged View of

Configuration Jumpers

Ch 2

Ch 4

Ch 6

Ch 8

Ch 1

Ch 3

Ch 5

Ch 7

Reposition the cover and secure with the four

screws removed in step 1.

19813

3