Setting the input filter jumpers – Rockwell Automation 1771-IQ16 DC (24V) Isolated Input Module Installation Instructions User Manual

Page 4

Advertising
background image

JPR1

JPR2

Filter Time Jumpers

JPR1 and JPR2 = Jumper for inputs 00 through 07

JPR3 and JPR4 = Jumper for inputs 10 through 17

JPR3

JPR4

0

1

0 1 0 1

0 1 0 1

Jumper in 0 position

10561-I

DC (24V) Isolated Input Module

4

Publication 1771-5.25 - November 1999

This module has four user-selectable filter time jumpers. Jumpers
JPR1 and JPR2 are used for filter times on inputs 00 through 07, and
jumpers JPR3 and JPR4 set filter times for inputs 10 through 17. The
jumper sets provide four different filter times as shown below.

Table B

Minimum and Maximum Filter Times

Filter Time

(ms)

Onto Off (ms)

Minimum Maximum

Off to On

0

0

0.56

µ

s

200

µ

s Typical

0.57

0.56

0.62

0.52 to 0.59ms

9.0

7.6

9.0

0.52 to 1.65ms

18.0

15.0

18.0

0.52 to 2.8ms

These filter times apply when the input is cycling from ON to OFF.
The OFF to ON filter time is fixed at 0.57ms.

To set the filtering time constant, proceed as follows:

1. Remove the side covers from the module circuit board by

removing the four screws securing the covers to the module and
remove the circuit board.

2. Position the jumpers as required to provide the filter time

constant you require.. Use your fingers to pull the jumper up and
position it on the two pins corresponding to your selection
(0 or 1).

Time Constant

(ms)

Inputs 00-07

Set Jumpers

JPR1 JPR2

Inputs 10-17

Set Jumpers

JPR3 JPR4

0

0

0

0

0

0.57 (factory default)

1

0

1

0

9.0

0

1

0

1

18.0

1

1

1

1

3. Reinstall the covers on the module circuit board and secure with

four screws.

Setting the Input Filter

Jumpers