Wiring – Rockwell Automation 1793-OB4E FLEX INTEGRA 4 PROTECTED OUTPUT User Manual
Page 4

4
FLEX Integra 4 Protected Output Module
Publication 1793-5.2 - January 2000
Wiring
This module is available with 2 styles of connectors; screw-cage and
spring-clamp. Refer to the wiring figure below.
1.
Connect individual output wiring to terminals 2 through 5 on row A.
2.
Connect associated common to terminals 10 through 13 on row B.
3.
Connect +24V dc voltage to terminal 8 on row B.
4.
Connect 24V dc common to terminal 0 on row A.
5.
If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal 15 to terminal 8 on the next
Integra module.
6.
If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal 7 on this module to
terminal 0 on the next Integra module.
.
!
ATTENTION:
Total current draw through the module’s
(+) voltage terminals is limited to 10A. Separate power
connections to the module may be required.