Setting the mode of the fuseblown jumper – Rockwell Automation 1771-OD16 AC (120V) ISO Output Installation Instructions User Manual

Page 4

Advertising
background image

AC (120V) Isolated Output Module, 16 Outputs

4

Publication 1771Ć5.21 -February 1997

Initial Handling Procedures

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and wiring arm before removing or
installing an I/O module.

Failure to remove power from the backplane or wir-
ing arm could cause module damage, degradation of
performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Touch a grounded object to rid yourself of charge before handling
the module.

Do not touch the backplane connector or connector pins.

When you configure or replace internal components, do not touch
other circuit components inside the module. If available, use a
static-safe work station.

When not in use, keep the module in its static-shield bag.

The fuse-blown jumper has two modes:

the preset, standard (STD) mode – displays the fuse status on
the red fuse-blown status indicator

the customer side indication (CSI) mode – displays the fuse
status in the input image table and on the red fuse-blown status
indicator. This mode configures the module as a 16 point output
module that utilizes both the output and input image data
tables
of your controller. When a fuse blows, all 16 bits in the
associated input image table will turn on (1).

For example, if you install the module in a PLCĆ5 system and address the module

as O:012, then the fuse status bits are in I:012.

To monitor the status of the module fuses, make certain that your
user program monitors the module’s input image table for ‘‘on” bits.

!

ATTENTION: Do not put the module jumper in
CSI mode when you use this module in a
complementary mode. Your system will not operate
properly.

Setting the Mode of the

FuseĆBlown Jumper

Advertising