20 MicroLogix 1200 RTD/Resistance Input Module

Publication 1762-IN014B-EN-P - July 2013

Input Specifications

Specification

1762-IR4

Input Types

100

Ω Platinum 385

200

Ω Platinum 385

500

Ω Platinum 385

1000

Ω Platinum 385

100

Ω Platinum 3916

200

Ω Platinum 3916

500

Ω Platinum 3916

1000

Ω Platinum 3916

10

Ω Copper 426

120

Ω Nickel 672

120

Ω Nickel 618

604

Ω Nickel-Iron 518

0…150

Ω

0…500

Ω

0…1000

Ω

0…3000

Ω

Converter Type

Sigma-Delta

Resolution

Input filter and configuration dependent.

Refer to the MicroLogix 1200 RTD/Resistance Input Module User
Manual, publication number

1762-UM003

, for more information.

Common Mode Rejection

110 dB minimum @ 50 Hz with the 10 or 50 Hz filter selected

110 dB minimum @ 60 Hz with the 10 or 60 Hz filter selected

Normal Mode Rejection Ratio

70 dB minimum @ 50 Hz with the 10 or 50 Hz filter selected

70 dB minimum @ 60 Hz with the 10 or 60 Hz filter selected

Non-linearity (in percent full-scale)

±0.05 %

Typical Accuracy

[Autocalibration Enabled] at 25 °C
(77 °F) Ambient with Module
Operating Temperature at 25 °C
(77 °F)

(1)

±0.5 °C (°F) for Pt 385
±0.4 °C (°F) for Pt 3916
±0.2 °C (°F) for Ni
±0.3 °C (°F) for NiFe
±0.6 °C (°F) for Cu

±0.15

Ω for 150Ω range

±0.5

Ω for 500Ω range

±1.0

Ω for 1000Ω range

±1.5

Ω for 3000Ω range

(1)

Accuracy is dependent upon the Analog/Digital converter filter rate selection, excitation current selection, data format, and
input noise.

Specification

1762-IR4

Typical Accuracy

[Autocalibration
Enabled] @ 0…55 °C
(32…131 °F)

±0.9 °C (°F) for Pt 385
±0.8 °C (°F) for Pt 3916
±0.4 °C (°F) for Ni
±0.5 °C (°F) for NiFe
±1.1 °C (°F) for Cu

±0.25

Ω for 150 Ω range

±0.8

Ω for 500 Ω range

±1.5

Ω for 1000 Ω range

±2.5

Ω for 3000 Ω range

Accuracy Drift @
0…55 °C (32…131°F)

±0.026 °C/°C (0.026 °F/°F) for Pt 385
±0.023 °C/°C (0.023 °F/°F) for Pt 3916
±0.012 °C/°C (0.012 °F/°F) for Ni
±0.015 °C/°C (0.015 °F/°F) for NiFe
±0.032 °C/°C (0.032 °F/°F) for Cu

±0.007

Ω/°C (0.012Ω/°F) for 150Ω range

±0.023

Ω/°C (0.041Ω/°F) for 500Ω range

±0.043

Ω/°C (0.077Ω/°F) for 1000Ω range

±0.072

Ω/°C (0.130Ω/°F) for 3000Ω range

Repeatability

(1)

±0.1 °C (±0.18 °F) for Ni and NiFe

±0.2 °C (±0.36 °F) for other RTD inputs

±0.04

Ω for 150Ω resistances

±0.2

Ω for other resistances

Excitation Current Source 0.5 mA and 1.0 mA selectable per channel

Open-Circuit Detection
Time

(2)

6…1212 ms

Channel Update Time

Input filter and configuration dependent. Refer to the MicroLogix 1200
RTD/Resistance Input Module User Manual, publication number

1762-UM003

, for

more information.