Programming

Chapter 3

3Ć33

Figure 3.27

General AF4 Log to Base 10 Function Word and Digit Format

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Digit 1

(MSD)

Digit 2

Bit No.

Data Address

m

Digit 2

Operand

Digit 5

Result Address

n

Result

D

E

n + 1

E = Enable Bit (1 = Function in Progress)

D = Done Bit (1 = Function Complete)
MSD = Most Significant Digit

LSD = Least Significant Digit

11499

Digit 3

(LSD)

Digit 3

Digit 1

(MSD)

Digit 4

Digit 6

(LSD)

ER = Error Bit (1 = Input is 0)

ER

3.

Enter a data address and a result address.

If we select a data address of 201 and a result address of 305, the AF4
establishes the data table format shown in Figure 3.28. The data address is
reserved for the three digits of the number whose log you want. The result
address, 305, is reserved for the first three digits of the resultant log; the next
higher address, 306, is reserved for the last three digits. The implied decimal
point in the result is after the MSD.

Figure 3.28

AF4 Log to Base 10 Function Format After Address Entry

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

Digit 1

(MSD)

Digit 2

Bit No.

Data Address

Digit 2

Operand

Digit 5

Result Address

Result

D

E

E = Enable Bit (1 = Function in Progress)

D = Done Bit (1 = Function Complete)
MSD = Most Significant Digit

LSD = Least Significant Digit

11500

Digit 3

(LSD)

Digit 3

Digit 1

(MSD)

Digit 4

Digit 6

(LSD)

ER = Error Bit (1 = Input is 0)

ER

201

305

306