Troubleshoot the Module
If the alphanumeric display and LED indicators do not sequence through the 
expected states refer to the following troubleshooting tables. The three 
bi-color (red/green) LED status indicators on the 1756-ENBT module 
provide diagnostic information about the module and its connections to the 
network.
NET (Network) Status Indicator
The Network Status LED provides the following information:
State
Status
Description
Off
Not Powered,
No IP Address
Module is not powered, or does not 
have an IP address.
• Verify there is chassis power and 
the module is completely inserted 
into the chassis and backplane.
• Make sure the module has been
configured.
Flashing Green
No Connections
Module has obtained an IP address, 
but has no established connections.
Green
CIP Connections
Module has an IP address and at least 
one established connection.
Flashing Red
Connection Timeout
One or more of the connections in 
which the module is the target has 
timed out.
Red
Duplicate IP Address
Module has detected that its IP 
address is already in use. Assign a 
unique IP address to the module.