General specifications – Rockwell Automation 1732E-XXXX Ethernet/IP 24Vdc 16 Input Modules User Manual
Page 20

20 ArmorBlock 16-Point EtherNet/IP Module, Series A
Publication
1732E-IN002B-EN-E - February 2011
Current on-state output, max
0.5 A – 1732E-16CFGM12x
2 A – 1732E-OB16M12
Current per module, max
8.0 A (all outputs)
Leakage current, off-state output, max
50
μ
A
Surge current per output, max
3.2 A for 10 ms, repeatable every 2 s –
1732E-16CFGM12x
6 A for 10 ms, repeatable every 2 s –
1732E-OB16M12x
Pilot duty rating
DC-14 Pilot Duty
General Specifications
Attribute
Value
Voltage, auxiliary power, max
30V DC
Voltage, auxiliary power, min
12V DC
Current, auxiliary power input, max per
module (pins 2, 3)
1.1 A
0.3 A – 1732E-OB16M12
Current, auxiliary power, max per
module (pins 1, 4 plus pins 2, 3)
8 A (pins 2, 3 for sensor source and module plus
pins 1, 4 for output loads)
Current, sensor source, per input, max
50 mA
Current, sensor source, per module,
max (pins 2, 3)
800 mA
Communication rate
EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment
LED indicators
Module status – red/green
Network status – red/green
Link status – green
Auxiliary power – green
I/O LED – yellow
ArmorBlock 2-Port EtherNet/IP Module – 1732E-16CFGM12x,
1732E-OB16M12