Module scan time – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual
Page 49

Module Programming
5-5
Publication 1771Ć6.5.116 - July 1996
Scan time is defined as the amount of time it takes for the input
module to read the input channels and place new data into the data
buffer.
Word 24 of the block transfer write data table shows the scan time
for the module for the given configuration. These figures are the time
it takes to sample all channels and process the data. Refer to
Appendix A for tables showing common scan times at various
oversample rates.
Table 10.A
Scan Time in SingleĆEnded Mode
Number of
Oversamples
Word 24
Time (ms)
0
798
7.98
1
392
3.92
2
451
4.51
4
567
5.67
8
798
7.98
16
1260
12.60
32
2183
21.83
64
4028
40.28
128
7718
77.18
256
15100
151.00
Table 10.B
Scan Time in Differential Mode
Number of
Oversamples
Word 24
Time (ms)
0
402
4.02
1
199
1.99
2
229
2.29
4
287
2.87
8
402
4.02
16
634
6.34
32
1096
10.96
64
2018
20.18
128
3864
38.64
256
7554
75.54
Module Scan Time