Chapter summary – Rockwell Automation 1771-IFF/A,D17716.5.116 FAST ANALOG INPUT MODULE User Manual

Page 67

Advertising
background image

7-5

Publication 1771Ć6.5.116 - May 1996

Figure 7.3

Block Transfer Read in Two's Complement - Data First Configuration, Differential

Inputs

Dec. Bits

15 14 13 12 11 10 09 08 07 06 05 04

03

02

01

00

Description

Octal Bits

17 16 15 14 13 12 11 10 07 06 05 04

03

02

01

00

Description

Word 1

Channel 1 Input

Channel 1 Input

2

Channel 2 Input

Channel 2 Input

3

Channel 3 Input

Channel 3 Input

4

Channel 4 Input

Channel 4 Input

5

Channel 5 Input

Channel 16 Input

6

Channel 6 Input

Channel 1 Input

7

Channel 7 Input

Channel 2 Input

8

Channel 8 Input

Channel 3 Input

9

HF EE CS RTS IS OR PU

Diagnostics

10

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data underrange for channels 1-16

1

11

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data overrange for channels 1-16

1

12

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Data polarity for channels 1-16

13

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Offset Calibration Results

14

16 15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

Gain Calibration Results

15

15Ćbit rolling counter - binary, 1ms resolution

Time Stamp

16

Update rate - binary, to 1

υ

s, with +4

µ

s resolution

Scan Time

17 - 24

Not used (0)

Where:

PU = Power up bit

OR= Out of range bit

IS = Invalid scaling bit

RTS = Real time sampling bit

HF = Hardware Fault

EE = EEPROM status bits

CS = Calibration status bits

1

These bits are set (1) at approximately the input range limits selected (Table NO TAG).

In this chapter you learned the meaning of the status information that
the input module sends to the processor.

Chapter Summary