2–5

Set up the Hardware

Publication 1785Ć10.3 - October 1996

Install the PLCĆ5 Processor

Define the DH+ Station Address of Channel 1A

by setting switch assembly SWĆ1 on the back of

the processor.

Install the processor.

To install the battery, slide the batteryĆside

connector into the processorĆside connector

until you hear them snap together, and attach

the battery cover.

side view

Set Switch

assembly SW1

address here

OFF

Battery Connector

Battery Cover

Battery

1

2

4

More

For detailed information about handling and disposing of the battery

as well as other important guidelines, see publication AGĆ5.4.

If you plan to install an EEPROM, install it now.

3

Memory module slot

ATTENTION: Do not insert or remove the EEPROM under power.

Insertion or removal under power can result in loss of

program memory and a processor fault.

Top view of processor

Locking

Bar

PLC-5/25

Processor

Card Guides

Lift Eector Tab

For more information, see the Classic PLC-5 Programmable
Controllers Hardware Installation Manual, publication number
1785-6.6.1.

Powerup the System

Powerup the system. Check the LED display on the processor. If
your system is operating properly, the PROC LED should be steady
red. If the PROC LED is not red, see chapter 4 for troubleshooting
information before you install the I/O modules.