4 - interpret the led indicators, Diagnostics, Chapter 4 – Rockwell Automation 1761-NET-AIC Advanced Interface Converter (AIC+) User Manual User Manual
Page 35: Interpret the led indicators, Chapter

31
Publication 1761-UM004B-EN-P - June 2006
Chapter
4
Interpret the LED Indicators
Diagnostics
LED Indicators and Selector Switch
LED Indicator Status
LED Indicator
Status
Condition
TX RS-232 9-pin
Flashing
Transmitting.
Off
Receiving or idle.
TX RS-232 8-pin
Flashing
Transmitting.
Off
Receiving or idle.
TX RS-485
Flashing
Transmitting.
Off
Receiving or idle.
PWR – Power OK
On
Power OK.
Off
No power to AIC+ interface converter or dc
source switch set incorrectly.
Power Source
Selection Switch
Cable
24V dc power supplied to AIC+ interface
converter from device connected to RS-232
(8-pin mini-DIN) communication port.
External
24V dc power supplied to AIC+ interface
converter from external source (use 24V dc
power from SLC or user-supplied 24V dc
power supply).
TX RS-232 (8-pin
mini-DIN) LED Indicator
DC Power-source
Selector Switch
PWR (Power) LED
Indicator
TX RS-485 LED Indicator
TX RS-232 (9-pin) LED
Indicator