Connect wiring for the 1794-tbn – Rockwell Automation 1794-IF4I FLEX I/O 4 Isolated Input Module User Manual

Page 3

Advertising
background image

FLEX™ I/O Isolated Input Analog Module 3

Publication 1794-IN038E-EN-P - November 2011

5. If continuing DC common to the next base unit, connect a jumper from

terminal 33 (common) on this base unit to terminal 16 on the next base
unit.

6. 1794-TB3T, 1794-TB3TS only: Connect cable shield to terminals 39…46

on row (C).

7. 1794-TB2, 1794-TB3, 1794-TB3S: Connect wiring shields to functional

earth ground as near as possible to the module.

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T and 1794-TB3TS Terminal Base
Wiring

Connect Wiring for the 1794-TBN

1. Connect individual input wiring to numbered terminals on row (B) as

indicated in the

Wiring Connections for the 1794-IF4I Input Module

table.

2. Connect the associated input common/return to the corresponding

terminal on row (C) for each input as indicated in the table.

3. Connect +V DC power to terminal 34 on row (C).
4. Connect DC common/return to terminal 16 on row (B).
5. If continuing power to the next terminal base, connect a jumper from

terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit.

6. If continuing DC common to the next base unit, connect a jumper from

terminal 33 (common) on this base unit to terminal 16 on the next base
unit.

7. Connect wiring shields to functional earth ground as near as possible to

the module.

Wiring Connections for the 1794-IF4I Input Module

Channel

Signal Type

Label
Markings

1794-TB2, 1794-TB3, 1794-TB3S,
1794-TB3T, 1794-TB3TS

1794-TBN

Terminal

Shield (1794-TB3T,
1794-TB3TS)

Terminal

0

Current

I0

A-0

C-39

B-0

Current

I0 ret

A-1

C-1

Voltage

V0

A-2

C-40

B-2

Voltage

V0 ret

A-3

C-3

1

Current

I1

A-4

C-41

B-4

Current

I1 ret

A-5

C-5

Voltage

V1

A-6

C-42

B-6

Voltage

V1 ret

A-7

C-7

2

Current

I2

A-8

C-43

B-8

Current

I2 ret

A-9

C-9

Voltage

V2

A-10

C-44

B-10

Voltage

V2 ret

A-11

C-11

3

Current

I3

A-12

C-45

B-12

Current

I3 ret

A-13

C-13

Voltage

V3

A-14

C-46

B-14

Voltage

V3 ret

A-15

C-15

-V DC common

1794-TB2, 1794-TB3, 1794-TB3S: Terminals B-16…B-33 are internally connected in the
terminal base unit.

1794-TBN: Terminals B-16 and B-33 are internally connected in the terminal base unit.

1794-TB3T, 1794-TB3TS: Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally
connected in the terminal base unit.

+V DC power

1794-TB3, 1794-TB3S: Terminals C-34…C-51 are internally connected in the terminal base
unit.

1794-TB3T, 1794-TB3TS: Terminals C-34, C-35, C-50 and C-51 are internally connected in the
terminal base unit.

1794-TB2, 1794-TBN: Terminals C-34 and C-51 are internally connected in the terminal base
unit.

Chassis ground
(shield)

1794-TB3T, 1794-TB3TS: Terminals C-39…C-46 are internally connected to chassis ground.

ATTENTION

Connect only one current or one voltage signal per channel. Do not
connect both current and voltage on one channel.

ATTENTION

Do not remove or replace a Terminal Base unit while power is applied.
Interruption of the backplane can result in unintentional operation or
machine motion.

I

+

+

-

+

+

-

I

+

I

+

-

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

45751

Row A
Row B
Row C

Current
input

Current
input

Current
input

Voltage
input

AC or DC

4-wire current
transmitter

DC only

3-wire current
transmitter

Current only

2-wire current
transmitter

DC only

3-wire
transmitter

Label placed at top of wiring area

Row A

Row B

Row C

1794-TB3S shown

Advertising