Status indicator, Specifications – Rockwell Automation 1794-IF4I FLEX I/O 4 Isolated Input Module User Manual

Page 5

Advertising
background image

FLEX™ I/O Isolated Input Analog Module 5

Publication 1794-IN038E-EN-P - November 2011

Status Indicator

The OK status indicator is two-colored: red and green. The indicator flashes green
for one of three reasons:

1. The module configuration word is zero (for example, power up reset

condition).

2. The 24V DC user power is off.
3. The module is in configuration mode.

The indicator displays red to indicate that the module did not pass the initial
hardware test. Cycle power again.
After power up, if the status indicator is not flashing green or solid green, cycle
module power once more to verify a proper reset of the bus interface.

Specifications

General Specifications

Attribute

Value

Number of inputs

4 isolated

Module location

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, 1794-TB3TS, and 1794-TBN

FlexBus voltage

5V DC

FlexBus current

50 mA

External DC power supply,
nom voltage range

24V DC

19.2…31.2V DC (includes 5% AC ripple)

External DC power supply
current

80 mA @ 24V DC

Thermal dissipation, max

6.8 BTU/hr @ 31.2V DC

Power dissipation, max

2.0 W @ 31.2V DC

Isolation voltage

120V (continuous), Basic Insulation Type, channel to channel, channel to user,
channel to system, and user power to system when used with 1794-TB2,
1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS.

250V (continuous), Basic Insulation Type, channel to channel, channel to user,
channel to system, and user power to system when used with 1794-TBN.

Type tested at 1000V AC for 60 s.

Data format

2’s complement

2’s complement %

Binary

Offset binary

Indicators

1 red/green power/status indicator

Keyswitch position

3

Dimensions, with module
installed in base; HxWxD

94.0 x 94.0 x 66.0 mm

(3.7 x 3.7 x 2.6 in.)

Conductor category

(1)

(1)

Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

2 – on signal ports

2 – on power ports

Conductor wire size

Determined by installed terminal base

Wire type

Shielded on signal ports

North American temp code

T4A

IEC temp code

T4

Module Specifications – 1794-IF4I

Attribute

Value

Resolution

Voltage

Current

16 bits – unipolar; 15 bits plus sign – bipolar

0.156 mV/cnt unipolar; 0.313 mV/cnt bipolar

0.320

A/cnt unipolar; 0.640 A/cnt bipolar

Conversion type

Sigma Delta

Update rate

2.5/5.0/7.5 ms all channels (see the

Input Update Rate for Real Time Sample

Interval = 0

table)

Input current terminal

4…20 mA (user configurable)

0…20 mA (user configurable)

±20 mA (user configurable)

Input voltage terminal

±10V (user configurable)

0…10V (user configurable)

±5V (user configurable)

0…5V (user configurable)

Step response to 63% of full
scale

1200 Hz conversion rate = 0.6 ms

600 Hz conversion rate = 6.7 ms

300 Hz conversion rate = 13.4 ms

150 Hz conversion rate = 26.7 ms

Input resistance voltage

Voltage terminal

Current terminal


>10 M



<100

(2)

Normal mode rejection ratio –
voltage or current terminal

-3 dB @ 12 Hz (300 Hz conversion rate)

-80 dB @ 50 Hz (300 Hz conversion rate)

-3 dB @ 6 Hz (150 Hz conversion rate)

-80 dB @ 60 Hz (150 Hz conversion rate)

Common Mode Rejection
Ratio

-120 dB @ 50/60 Hz

Absolute accuracy

(1)

Voltage terminal

Current terminal


0.1% full scale @ 25 °C

0.1% full scale @ 25 °C

Accuracy drift w/temperature

Voltage terminal

Current terminal


0.0028% full scale/°C

0.0038% full scale/°C

Calibration required

Factory-calibrated. Can be calibrated in field when necessary.

Maximum overload

30V continuous or 32 mA continuous, one channel at a time.

(1)

Includes offset, gain, non-linearity and repeatability error terms.

(2)

If 24V DC is removed from the module, input resistance = 10 k

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, surrounding air,
max.

55 °C (131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock):

50 g

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on power ports

±2 kV @ 5 kHz on shielded signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports

±2 kV line-earth(CM) on shielded signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Certifications (when product is marked)

(1)

Attribute

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL

File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified

for U.S. and Canada. See UL File E194810.

CSA

CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D

Hazardous Locations. See CSA File LR69960C.

Ex

European Union 94/9/EC ATEX Directive, compliant with:

EN 60079-15; Potentially Explosive Atmospheres, Protection "n"

EN 60079-0; General Requirements

II 3 G Ex nA IIC T4 X

Module Specifications – 1794-IF4I

Advertising