Communicate with Your Module 3-5
The following table shows the Instance Services provided by the
Parameter Object (Attribute = 1).
Operating Modes
The operating modes of the 1734-SSI module are essentially the
parameters you set through the RSNetWorx EDS file. This table lists
parameters you set.
Parameter
Services
Field
Bytes
1
Get
Present SSI Word
4
2
Latched SSI Word
4
3
SSI Status Word
2
4
Get/Set
Run
1
5
Gray/Binary
1
6
SSI Word Length
1
7
Data Rate
1
8
Gray to Binary Conversion
1
9
SSI Word Delay Time
2
10
Standardization
1
11
Trailing Bits
1
12
Latch Input Control
1
13
Sensor Resolution
2
14
Sensor Cycles
2
15
Comp 1 Control
1
16
Comparator 1 Value
4
17
Comp 2 Control
1
18
Comparator 2 Value
4
19
SSI Word Filter Control
(1)
(1)
This parameter is present in firmware version 4.001 and later.
1
Parameter
Value
(1)
Notes
Run
Enable/Disable
Turns SSI data clock on or
off
Data Type
Binary or Gray
SSI sensor’s data type
Data Word Length
2…31 (13)
Length of the received serial
data word can be any size
between 2 and 31 data bits.
Bit 32 is used for Latch Input
detection.
Data Rate
125/250/500K baud,
1/2M baud
Speed of SSI data clock