Wire the Relay Cartridge

1. Detach the 4-pin clamp-style removable connector from the relay

cartridge and connect wiring as shown below:

,PSRUWDQW

The required wire diameter specification for the relay
cartridge is 12-22 AWG. The wire must be solid,
stranded or fine stranded copper. The maximum length
between the connector and power source/relay must
be less than 10 meters (unless all circuit components,
modules and the power source are located within the
same NEMA enclosure).

,PSRUWDQW

As shown in the wiring diagram below, you must
install both of the following:

an external FLM, slo-blo 0.5A fuse in series with the L1 line

connecting to the 4-pin ARI connector, and

a surge suppressor (such as Allen-Bradley cat. nos. 700-N5 or -

N24) across the external 700P relay coil

2. Reattach the wired connector to the relay cartridge.

4-pin removable
connector

FLM 0.500A fuse
(customer-installed)

L1

120V

AC

N

(L2)

Surge supressor
(customer-installed)

700P Relay