How the relay cartridge works – Rockwell Automation 1785-RC Application Relay Interface Installation Instruction User Manual
Page 6
 
3/& 5HOD\ &DUWULGJH
Qiyvphvà &'$DI 6VTQГГ6 vyГ!
,PSRUWDQW
When the relay cartridge internal relay coil switches (from 
open to closed, or closed to open), you must wait at least 50ms 
before acting on the internal relay contact status bit 2. The 
Internal Relay Contact Status indicator may briefly flash RED 
during this time.
,PSRUWDQW
You must qualify relay contact status bit 2 with the relay 
cartridge 120Vac external power valid bit 0 to assure correct 
internal relay contact status.
,PSRUWDQW
Relay contact status bit 2 is filtered by the controller’s 
firmware. The firmware reads the relay contact status circuit 
each program scan. Status bit 2 is updated only after two 
successive reads return the same logic level of status. The 
update time of status bit 2 will vary depending on program 
scan time.
 Bit 3 - this bit is set whenever the relay cartridge is resident in the PLC-5 
controller.
How the Relay Cartridge Works
The relay cartridge is designed to open a relay contact whenever
 the PLC-5 controller detects specific software operation requests, such as:
•
a ladder program edit request from RSLogix5, AI5 or 6200 series 
software - this includes ladder rung inserts, deletes, modifications or 
modifying processor’s name and/or program file names.
•
a change to the state of I/O forces - including changing the state of 
force bits in the force table and enabling or disabling I/O forces.
,PSRUWDQW
ALL I/O Force requests will be delayed for one second 
before the request becomes active.
When the controller is in Run, Remote Run or Remote Test mode, and 
any of the above requests are detected by the controller, it will open the 
relay contact for one second.
When the controller is in Program or Remote Program mode, the relay 
is returned to its normal ON or contact closed state.