Wiring – Rockwell Automation 1793-IB2XOB2PS FLEX INTEGRA 2 INPUT/2 PROTECTED OUTPUT MODUL User Manual

Page 4

Advertising
background image

4

FLEX Integra 2 Input/2 Protected Output Module

Publication 1793-5.3 - September 1999

Wiring

This module is available with 2 styles of terminations; 1794-IB2XOB2P -
screw-cage and 1793-IB2XOB2PS - spring-clamp. Refer to the wiring
figure below.

1.

Connect individual sensor input leads to terminals 2 (channel 0) and 3

(channel 1) on row A.

2.

Connect sensor supply lead to +24V dc (terminals 1, 6, 9, or 14).
(Terminals 1, 6, 8, 9, 14 and 15 are connected internally to +24V dc.)

3.

Connect associated input common (3-wire sensors only) to terminals
10 and 11 on row B.

4.

Connect individual output wiring to terminals 4 (channel 0) and 5

(channel 1) on row A.

5.

Connect associated output common to terminals 12 and 13 on row B.

6.

Connect +24Vdc voltage to terminal 8 on row B

7.

Connect 24V dc common to terminal 0 on row A.

8.

If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal 15 to terminal 8 on the next
FLEX Integra module.

9.

If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal 7 on this module to
terminal 0 on the next Integra module.

.

!

ATTENTION:

Total current draw through the module’s

(+) voltage terminals is limited to 10A. Separate power
connections to the module may be required.

1793-IB2XOB2P

1793-IB2XOB2PS

0

1

2

3

4

5

6

7

8

9

10

11

A

B

13

14

15

12

41468

C

V

C

V

C

C

V

V

C

C

V

V

O

O

I

I

Ch 0 Ch 1

Ch 0 Ch 1

0

1 2 3 4 5 6

7

8 9 10 11 12 13 14 15

A

B

41469

C V

C

V

C C

V

V

C C

V

V

O O

I

I

Ch 0 Ch 1

Ch 0 Ch 1

Where: C - common, V = + voltage, I = input, O = output

Advertising
This manual is related to the following products: