Rockwell Automation 1793-IB2XOB2PS FLEX INTEGRA 2 INPUT/2 PROTECTED OUTPUT MODUL User Manual

Page 9

Advertising
background image

FLEX Integra 2 Input/2 Protected Output Module

9

Publication 1793-5.3 - September 1999

Specifications - 2 Input/2 Protected Output Module Cat. No. 1793-IB2XOB2P
and -IB2XOB2PS

Module Type

2 input/2 output digital combination w/electronic fusing
1793-IB2XOB2P - screw-clamp terminations
1793-IB2XOB2PS - spring-clamp terminations

Module Location

DIN rail mounting

Number of Channels

2 digital input - sinking/2 digital output - sourcing,
protected

Input

On-state Voltage

10-31.2V dc; 24V dc nominal

On-state Current

2-12 mA; 8mA @ 24V dc

Off-state Voltage

5V dc maximum

Off-state Current

1.5mA minimum

Channel Impedance

4.6K

Ω

Isolation Voltage

Channel to system - 850V dc for 1s
Channel to channel - None

Input Delay - selectable

Off to On
On to Off

512

μs, 1, 2, 8, 16, 32 or 64ms

512

μs, 1, 2, 8, 16, 32 or 64ms

Default = 512

μs

Output

On-state Voltage

10-31.2V dc; 24V dc nominal

On-state Current

1-500mA per channel

Off-state Voltage

31.2V dc maximum

Off-state Current

0.5mA maximum leakage

Channel Impedance

1.0

Ω (0.5V dc maximum drop)

Surge Current

1.5A for 50ms, repeatable every 2s

Isolation Voltage

Channel to system - 850V dc for 1s
Channel to channel - None

Delay Time

Off to On
On to Off

0.5ms maximum
1.0ms maximum

General

Flexbus Current

20mA maximum

Power Dissipation

1.4W @ 31.2V dc

Thermal Dissipation

4.8 BTU/hr @ 31.2V dc

Indicators

4 yellow channel status indicators

External dc Power Voltage

Current

19.2-31.2V dc (5% ac ripple)
40mA maximum

Advertising
This manual is related to the following products: