Rockwell Automation 1762-IQ8OW6 DC-Input/Relay-Output Combination Module User Manual
Page 14

14 DC-Input/Relay-Output Combination Module
Publication 1762-IN018B-EN-P - July 2013
Output Specifications
Specification
Value
Voltage Range
5…265V AC
5…125V DC
Commons per Module
6
Output Type
6-Form A (normally open)
Signal Delay Time
On-delay: 10 mS (max) Off-delay: 10 mS (max)
Off Leakage Current
0 mA
On-state Current (Min.)
10 mA @ 5V DC
Continuous Current per Point
See table on page 14.
Continuous Current per Module
8 A
Total Controlled Load
1440VA/Module max
Relay Contact Ratings
Volts (max.)
Continuous
Amps per
Point (Max.)
Amperes
(1)
(1)
Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Voltamperes
Make
Break
Make
Break
240V AC
2.5 A
7.5 A
0.75 A
1800VA
180VA
120V AC
15 A
1.5 A
125V DC
1.0 A
0.22 A
(2)
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.
28VA
24V DC
2.0 A
1.2 A
28VA