Output Specifications

Specification

Value

Voltage Range

5…265V AC
5…125V DC

Commons per Module

6

Output Type

6-Form A (normally open)

Signal Delay Time

On-delay: 10 mS (max) Off-delay: 10 mS (max)

Off Leakage Current

0 mA

On-state Current (Min.)

10 mA @ 5V DC

Continuous Current per Point

See table on page 14.

Continuous Current per Module

8 A

Total Controlled Load

1440VA/Module max

Relay Contact Ratings

Volts (max.)

Continuous
Amps per
Point (Max.)

Amperes

(1)

(1)

Surge Suppression - Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Voltamperes

Make

Break

Make

Break

240V AC

2.5 A

7.5 A

0.75 A

1800VA

180VA

120V AC

15 A

1.5 A

125V DC

1.0 A

0.22 A

(2)

(2)

For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.

28VA

(2)

24V DC

2.0 A

1.2 A

28VA

(2)