Rockwell Automation 1762-IQ8OW6 DC-Input/Relay-Output Combination Module User Manual
Page 15

DC-Input/Relay-Output Combination Module 15
Publication 1762-IN018B-EN-P - July 2013
General Specifications
Specification
Value
Dimensions, HxWxD
90 x 40.4 x 87 (3.54 x 1.59 x 3.43 in.)
height including mounting tabs is 110 mm (4.33in.)
Approximate Shipping Weight
(with carton)
280g (0.62 lbs.)
Bus Current Draw, (Max)
110 mA @ 5V DC
80 mA @ 24V DC
Heat Dissipation
5.0 W @ 30V DC
4.4 W @ 26.4V DC
(The Watts per point, plus the minimum W, with all points energized.)
Power Supply Distance Rating
6
Isolated Group
Group 1 (input 0…3) Group 2 (input 4…7) Group 3 (output 0…5)
Vibration
Operating: 10…500 Hz, 5 g, 0.030 in. max. peak-to-peak,
2 hours per axis.
Relay Operation: 1.5 g
Shock
Operating: 30 g panel mounted, 3 pulses per axis
Relay Operation: 7 g
Non-Operating: 50 g panel mounted, 3 pulses per axis
(40 g DIN Rail mounted)
Vender ID Code
1
Product Type Code
7
Product Code
98
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
ISA/ANSI 12.12.01
(C-UL under CSA C22.2 No. 213)
Radiated and Conducted
Emissions
EN50081-2 Class A
ESD Immunity (IEC1000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3)
10 V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed
carrier
Fast Transient Burst (IEC1000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC1000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
10V, 0.15…80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is
30…1000 MHz.