FLEX Integra 16 Protected Sink Output Module

Publication 1793-5.11 - December 1999

Wiring

This module is available with 2 styles of connectors; screw-cage
(1793-OV16P) and spring-clamp (1793-OV16PS). Refer to the wiring
figure below.

1.

Connect individual output wiring to terminals 0 through 15 on row A.

2.

Connect associated power terminal to terminals on row B.

3.

Connect +24V dc voltage to terminal V on row B.

4.

Connect 24V dc common to terminal COM on row A.

5.

If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal V to terminal 8 on the next 8
point Integra module or terminal V on the next 16 point Integra
module.

6.

If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module
to terminal 0 on the next 8 point Integra module or to terminal COM
on the next 16 point Integra module.

.

!

ATTENTION:

Total current draw through the module’s

(V) voltage terminals is limited to 10A. Separate power
connections to the module may be required.

1793-OV16P

1793-OV16PS

0

1

2

3

4

5

6

7

8

9

10

11 12 13

14 15

A

B

41814

V

V

COM

COM

A

B

0

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15 COM

COM

V

V

41816

Where: COM = common, V = + 24V dc, 0 thru 15 = outputs