Wiring – Rockwell Automation 1793-OV16 Flex Integra Output Module Install Inst User Manual
Page 4

4
FLEX Integra 16 Protected Sink Output Module
Publication 1793-5.11 - December 1999
Wiring
This module is available with 2 styles of connectors; screw-cage
(1793-OV16P) and spring-clamp (1793-OV16PS). Refer to the wiring
figure below.
1.
Connect individual output wiring to terminals 0 through 15 on row A.
2.
Connect associated power terminal to terminals on row B.
3.
Connect +24V dc voltage to terminal V on row B.
4.
Connect 24V dc common to terminal COM on row A.
5.
If daisy-chaining +24V dc from this module to the next FLEX Integra
module, connect a jumper from terminal V to terminal 8 on the next 8
point Integra module or terminal V on the next 16 point Integra
module.
6.
If daisy-chaining 24V dc common from this module to the next FLEX
Integra module, connect a jumper from terminal COM on this module
to terminal 0 on the next 8 point Integra module or to terminal COM
on the next 16 point Integra module.
.
!
ATTENTION:
Total current draw through the module’s
(V) voltage terminals is limited to 10A. Separate power
connections to the module may be required.
1793-OV16P
1793-OV16PS
0
1
2
3
4
5
6
7
8
9
10
11 12 13
14 15
A
B
41814
V
V
COM
COM
A
B
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 COM
COM
V
V
41816
Where: COM = common, V = + 24V dc, 0 thru 15 = outputs