Output Signal Delay Time

Off to On
On to Off

0.5ms maximum
1.0ms maximum

Flexbus Current

80mA maximum

Power Dissipation

4.2W @ 31.2V dc

Thermal Dissipation

14.3 BTU/hr @ 31.2V dc

Indicators

16 yellow channel status indicators

Fusing

Outputs are electronically protected

External dc Power Voltage

Current

19.2-31.2V dc (5% ac ripple)
49mA

Dimensions

Inches

(Millimeters)

2.72H x 3.7D x 3.2W
(69H x 94D x 80W)

Environmental Conditions

Operational Temperature
Storage Temperature
Relative Humidity
Shock

Operating
Nonoperating

Vibration

0 to +55

o

C (32 to +131

o

F)

-40 to +85

o

C (-40 to +185

o

F)

5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+1)ms pulse width
Tested to 50g peak acceleration, 11(+1)ms pulse width

Tested 5g @ 10-500Hz per IEC68-2-6

Conductors

Wire Size

Category

12 gauge to 18 gauge (4mm

2

to 0.75mm

2

)

stranded wire rated @ 75

o

C minimum

3/64 in (1.2mm) maximum insulation

2

1

Screw Terminal Torque

5-7 lb-in (0.5-0.6Nm)

Agency Certification
(when product is marked)

• C-UL Listed

• C-UL Class I, Division 2 Groups A, B, C and D certified

• UL listed

• CE marked for all applicable directives

• C-Tick marked for all applicable acts

1

Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”

Specifications - 16 Protected Output Module Cat. No. 1793-OV16P and -OV16PS