Rockwell Automation 1734D-1B8XOW8S 8 Input/8 Relay Output Module Installation Instructions User Manual
Page 12
Advertising

12 POINTBlock dc 8 Input/8 Relay Output Module
Publication
1734-IN021C-EN-P - September 2006
Channel, Input Terminal, Common, and Voltage for Terminal Blocks
Channel
Input Terminal
Common
Voltage
Removable Terminal Block 0
0…3
No Connection
No Connection
4, 5
Common
6, 7
Vin
Removable Terminal Block 1
Channel
Input Terminal
Common
Voltage
0
0
4
6
1
1
5
7
2
2
4
6
3
3
5
7
Removable Terminal Block 2
Channel
Input Terminal
Common
Voltage
4
0
4
6
5
1
5
7
6
2
4
6
7
3
5
7
Connect common on 3-wire proximity switches.
12/24V dc is supplied through the internal power bus.
IMPORTANT
When connecting more than one wire in a termination point,
make sure that both wires are the same gauge and type.