FLEX I/O Remote I/O Adapter
4
Publication 1794Ć5.11 - November 1996
Wiring
1 SH 2
D
F
G
E
20131
24V
COM
AllenĆBradley
24 VDC
POWER SUPPLY
RIO ADAPTER
1794-ASB2
ADAPTER
ACTIVE FAULT
LOCAL
FAULT
1. Connect the remote I/O cable to the removable remote I/O connector.
Connect
To
Blue Wire - RIO
1
Shield Wire - RIO
SH
Clear Wire - RIO
2
2. Connect +24V dc input to the left side of the lower connector,
terminal E.
3. Connect 24V common to the left side of the upper connector,
terminal D.
4. Connections G and F are used to pass 24V dc power (G) and 24V
common (F) to the next module in the series (if required).