Rockwell Automation 1794-ASB Remote Flex I/O Adapter Installation Instructions User Manual
Page 8

FLEX I/O Remote I/O Adapter
8
Publication 1794Ć5.11 - November 1996
S1 Switch Position
Rack Number
1
2
3
4
5
6
PLC-3
PLC-5/250
PLC-5
PLC-2 &
1771ĆSN
1747ĆSN
Rack 55
OFF
ON
OFF
OFF
ON
OFF
Rack 56
ON
OFF
OFF
OFF
ON
OFF
Rack 57
OFF
OFF
OFF
OFF
ON
OFF
Rack 60
ON
ON
ON
ON
OFF
OFF
Rack 61
OFF
ON
ON
ON
OFF
OFF
Rack 62
ON
OFF
ON
ON
OFF
OFF
Rack 63
OFF
OFF
ON
ON
OFF
OFF
Rack 64
ON
ON
OFF
ON
OFF
OFF
Rack 65
OFF
ON
OFF
ON
OFF
OFF
Rack 66
ON
OFF
OFF
ON
OFF
OFF
Rack 67
OFF
OFF
OFF
ON
OFF
OFF
Rack 70
ON
ON
ON
OFF
OFF
OFF
Rack 71
OFF
ON
ON
OFF
OFF
OFF
Rack 72
ON
OFF
ON
OFF
OFF
OFF
Rack 73
OFF
OFF
ON
OFF
OFF
OFF
Rack 74
ON
ON
OFF
OFF
OFF
OFF
Rack 75
OFF
ON
OFF
OFF
OFF
OFF
Rack 76
ON
OFF
OFF
OFF
OFF
OFF
Not Valid
OFF
OFF
OFF
OFF
OFF
OFF
Rack address 77 is an illegal configuration.
PLCĆ5/11 processors can scan rack 03.
PLCĆ5/15 and PLCĆ5/20 processors can scan racks 01-03.
PLCĆ5/25 and PLCĆ5/30 processors can scan racks 01-07.
PLCĆ5/40 and PLCĆ5/40L processors can scan racks 01-17.
PLCĆ5/60 and PLCĆ5/60L processors can scan racks 01-27.
PLCĆ5/80 processors can scan racks 01-27.
PLCĆ5/250 processors can scan racks 00-37.