System wiring guidelines, Wiring output devices – Rockwell Automation 1769-OF4VI CompactLogix Module User Manual
Page 13
 
Compact 1769-OF4VI Isolated Analog Output Module 13
Rockwell Automation Publication 1769-IN076B-EN-P - August 2010
System Wiring Guidelines
Consider the following when wiring your system:
•
Channels are isolated from each other.
•
Use Belden 8761, or equivalent, shielded wire.
•
Under normal conditions, the drain wire and shield junction must be 
connected to earth ground, via a panel or DIN rail mounting screw at 
the analog I/O module end. Keep the shield connection to ground as 
short as possible.
•
For optimum accuracy, limit overall cable impedance by keeping your 
cable as short as possible. Locate the I/O system as close to your sensors 
or actuators as your application will permit.
•
Load resistance for each voltage output channel must be equal to or 
greater than 2K 
Ω
..
Wiring Output Devices
TIP
In environments where high frequency noise may be present, it 
may be necessary to ground the shield via a 0.1 µF capacitor at 
the load end and also ground the module end without a capacitor.
ATTENTION: Miswiring of the module to an AC/DC source will 
damage the module.
Be careful when stripping wires. Wire fragments that fall into a 
module could cause damage at power up. Once wiring is complete, 
ensure the module is free of all metal fragments.