16 Compact 1769-OF4VI Isolated Analog Output Module
Rockwell Automation Publication 1769-IN076B-EN-P - August 2010
Wiring the Finger-safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1.
Loosen the terminal screws to be wired.
2.
Route the wire under the terminal pressure plate. You can use the bare 
wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade 
lug.
3.
Tighten the terminal screw making sure the pressure plate secures the 
wire. Recommended torque when tightening terminal screws is
0.68 N•m (6 in•lb).
TIP
The terminal screws are non-captive. You can use a ring lug 
[maximum 6.35 mm (0.25 in.) o.d. with a 3.53 mm (0.139 in.) 
minimum i.d. (M3.5)] with the module.
TIP
If you need to remove the finger-safe cover, insert a screwdriver 
into one of the square wiring holes and gently pry the cover off. If 
you wire the terminal block with the finger-safe cover removed, 
you will not be able to put it back on the terminal block because 
the wires will be in the way.