18 ControlNet NetChecker

Rockwell Automation Publication 1788-UM001B-EN-P - August 2012

Check the Signal Level by Using the Bargraph

Set slide switch SW3 to its bargraph (rightmost) position and set the Node Finder to zero to get
a global level indication. Press the ON switch and make sure that the TRAFFIC status indicator
is green. Generally, the bargraph displays two green status indicators indicating the maximum
and the minimum level of signal seen at the point of test on the network. Normally, these should
be in the range of status indicators 2…6.

TRAFFIC

Low Bat

1

Node On Line

Diagnostic

2

3

4

5

6

7

L M H

Threshold

INPUT

Rockwell

Automation

Push ON

Buzzer

Ext

5VDC
0.25A

Power

Max

Min

0

7

Signal

(x1/4 )

GND

Trigger

Output to Scope

Node Finder

Power Switch

OFF
ON
Push ON

Bargraph

Pass/Fail

Slow Edges

Illegal Framing

Poor Signal
Quality

Allen-

ControlNet

TM

NetChecker

TRAFFIC

Low Bat

1

Node On Line

Diagnostic

2

3

4

5

6

7

L M H

Threshold

INPUT

Rockwell

Automation

Push ON

Buzzer

Ext

5VDC
0.25A

Power

Max

Min

1

1

Signal

(x1/4 )

GND

Trigger

Output to Scope

Node Finder

Power Switch

OFF
ON
Push ON

Bargraph

Pass/Fail

Slow Edges

Illegal Framing

Poor Signal
Quality

Allen-

ControlNet

TM

NetChecker

Allen-Bradley

Allen-Bradley

Green

Green

Red

Blinking Red

Low Threshold Setting (highest sensitivity level)

High Threshold Setting (lowest sensitivity level)

Advertising