Rockwell Automation 1747-AENTR SLC to EtherNet/IP Adapter Installation Instructions User Manual
Page 10

10 SLC 500 EtherNet/IP Adapter
Publication 1747-IN521B-EN-E - January 2013
Connect Your Adapter to the Ethernet/IP Network through
RJ-45 Connection
Connect your 1747-AENTR adapter module to an Ethernet/IP network as shown below:
Wire the RJ-45 connectors as shown.
To connect the module to the network, follow these steps:
ATTENTION: Do not force the module into the backplane connector. If you cannot
seat the module with firm pressure, check the alignment. Forcing the module can
damage the backplane connector or the module.
IMPORTANT
The 1747-AENTR device should always be installed in Slot 0. There should
only be one 1747-AENTR device installed within the same rack or its
connected rack extensions for multiple chassis support.
WARNING: If you connect or disconnect the communication cable with power
applied to this module or any device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
1
8
8
1
Signal
1
TxData+
2
TxData-
3
Recv Data+
4
Reserved
5
Reserved
6
Recv Data-
7
Reserved
8
Reserved
1747-AENTR module bottom view
RJ-45 connectors
RJ-45
45844