Rockwell Automation 1747-AENTR SLC to EtherNet/IP Adapter Installation Instructions User Manual
Page 10
 
10 SLC 500 EtherNet/IP Adapter
Publication 1747-IN521B-EN-E - January 2013
Connect Your Adapter to the Ethernet/IP Network through 
RJ-45 Connection
Connect your 1747-AENTR adapter module to an Ethernet/IP network as shown below:
Wire the RJ-45 connectors as shown. 
To connect the module to the network, follow these steps:
ATTENTION: Do not force the module into the backplane connector. If you cannot 
seat the module with firm pressure, check the alignment. Forcing the module can 
damage the backplane connector or the module. 
IMPORTANT
The 1747-AENTR device should always be installed in Slot 0. There should 
only be one 1747-AENTR device installed within the same rack or its 
connected rack extensions for multiple chassis support. 
WARNING: If you connect or disconnect the communication cable with power 
applied to this module or any device on the network, an electrical arc can occur. 
This could cause an explosion in hazardous location installations. Be sure that 
power is removed or the area is nonhazardous before proceeding.
1
8
8
1
Signal
1
TxData+
2
TxData-
3
Recv Data+
4
Reserved
5
Reserved
6
Recv Data-
7
Reserved
8
Reserved
1747-AENTR module bottom view
RJ-45 connectors
RJ-45
45844